Laserfiche WebLink
Sec. 15.04.120. - Section 1809.5 amended —Frost protection. <br />Item 1 of Section 1809.5 of the International Building Code shall be <br />amended to read as follows: <br />Extending 36 inches below finished grade; <br />Sec. 15.04.130.- Section 2704 added- Energy Storage Systems ESS <br />Chapter 27 of the International Building Code is amended by the <br />addition of a new Section 2704 to reads as follows: <br />2704. Lithium Energy Storage Systems (ESS). <br />2704.1 Lithium Energy Storage Systems (ESS). Energy <br />storage systems shall not be installed inside the thermal building envelope <br />of a commercial structure, primary residence, or Accessory Dwelling Unit <br />(ADU). The ESS shall be installed on the outside of the thermal envelope <br />or in an exterior insulated shed attached or detached to the building <br />envelope to protect from extreme heat and cold . The ESS shall have <br />electrical disconnects within 3 to 6 ft of the ESS. Installation of an ESS in <br />garages that are attached to a residence or ADU must have One Hour Fire <br />rated walls and ceiling and or an approved Fire Suppression system in the <br />garage. The ESS shall be installed on the wall farthest away from the <br />residence inside the garage the ESS shall have a Heat Detector that is tied <br />into the Smoke Detectors and shall have a flashing light on the battery with <br />the fault. <br />EXCEPTION: <br />1. Commercial Buildings with a 1 hour rated room where mechanical <br />ventilation is separate from the rest of the building and shall have a Heat <br />Detector at each battery with a flashing light on the battery with the fault. <br />Sec.15.04.140.- Section 3001.1 amended —Scope. <br />Section 3001.1 of the International Building Code is amended to read <br />as follows: <br />3001.1 Scope. This chapter governs the design, construction, <br />installation, alteration and repair of elevators and conveying systems and <br />their components. All elevators that serve accessible residential units shall <br />Ordinance No. 1907, Series 2025 <br />Page 8 of 59 <br />