Laserfiche WebLink
S28. Show size, spacing, spans, and directions of floor joists, beams, girders <br />and posts. <br />Additional Structural Comments: <br />ELECTRICAL: <br />El. Note on plans: All electrical installations shall comply with the <br />2018 IRC & 2017 NEC. <br />E2. All receptacles serving kitchen countertops, in garages, baths, <br />unfinished basements and outside receptacles shall be GFCI protected. - <br />IRC E3902 <br />E3. Lights in closets must comply with the clearance dimensions of IRC <br />E4003.12. <br />E4. Electrical panels must comply with IRC E3405 for 30" by 36" working <br />space and 6'-6" headroom. Show location. <br />E5. Show smoke detectors conforming to IRC section R314. All levels, all <br />bedrooms, access to all bedrooms and in all rooms with sloped ceilings <br />next to halls serving bedrooms. All detectors shall be hard -wired, <br />interconnected, and have battery backup. <br />E6. Show at least two outside grade level receptacles — one in the front <br />yard and one in the rear yard. -IRC E3901.7 <br />Reference at deck locations. <br />E7. All branch circuits that supply electrical in bedrooms need to be <br />provided with arc -fault protection. Show this on plans. IRC E3902.11. <br />More than just the bedrooms are required to be arc -fault protected. <br />E8. Carbon Monoxide detectors shall be installed in each habitable level <br />and no greater thanl5 feet from the bedroom door or within the bedroom <br />if a gas fired appliance is used in the bedroom or connected room off of <br />Page 15 of 21 <br />