Laserfiche WebLink
APPENDIX PT <br />MODELING TO A PERFORMANCE TARGET <br />PT101 Scope. This section establishes criteria for demonstrating compliance with <br />a performance target, and is required for new multifamily. (�pancy R-2), <br />offices greater than 5,000 ft2, primary and secondary schools, parking_ garages, <br />and warehouses. All end use load components within and associated with the <br />building and their building sites shall be modeled. <br />PT102 Mandatory requirements. The requirements in this section are <br />mandatory requirements and shall be required in addition to the provisions of <br />ASHRAE 90.1 Appendix G. <br />PT103 Performance target. Projects of the types listed in Table PT103 shall <br />demonstrate that the proposed design reaches a fixed energy use intensity (( I) <br />less than or equal to the values in Table PT103, calculated utilizing the energy <br />modeling procedures of Appendix G of ASHRAE 90.1. For building <br />multiple occupancy types, the modeled performance target shall be a weighted <br />average of the floor area of each occupancy_ type. <br />Exception: Energy used for electric vehicle charging, data centers, and <br />process loads shall be excluded from compliance modeling_ <br />TABLE PT103 <br />PERFORMANCE TARGETS <br />BUILDING TYPE <br />PERFORMANCE <br />TARGET <br />(kBTU/ft2) <br />Multifamily (Occupancy R-2) <br />32 <br />Office, small (>5,000 ft2) <br />19 <br />Office, medium (5,000 — 50,000 ft2) <br />23 <br />Office, large (>50,000 ft2) <br />28 <br />School, primary <br />34 <br />School, secondary <br />31 <br />Warehouse <br />11 <br />