City of Louisville's Prescriptive Compliance. The Prescriptive Compliance option <br />requires compliance with Sections C401.3, C401.4, C402 through C406, and Section <br />C408. <br />Core and shell buildings shall be required to comply with the provisions of Section <br />C402.1.3 through C402.5 of the 2021 International Energy Conservation Code. <br />6. Section C401.2.2 ASHRAE 90.1, is hereby deleted in its entirety. <br />7. A new Section C401.4 Mandatory Requirements for Commercial Buildings, is <br />hereby added to read as follows: <br />C401.4 Mandatory Requirements for Commercial Buildings. Commercial <br />buildings must comply with Table C401.4. <br />Table C401.4 (Mandatory) <br />Requirements for Commercial Buildings <br />Title <br />IECC Section <br />Air leakage <br />C402.5 <br />Calculation of heating and cooling loads <br />C403.1.1 <br />Data centers <br />C403.1.2 <br />System Design <br />C403.2 <br />Heating and cooling equipment <br />efficiency <br />C403.3 <br />Heating and cooling system controls <br />C403.4, except C403.4.3, <br />C403.4.4, C403.4.5 <br />Economizer fault detection and <br />diagnostics <br />C403.5.5 <br />Ventilation and exhausts stems <br />C403.7, except C403.7.4.1 <br />Fan and fan controls <br />C403.8, except C403.8.6 <br />Large diameter ceiling fans <br />C403.9 <br />Refrigeration equipment erformance <br />C403.11, except C403.11.3 <br />Construction of HVAC system elements <br />C403.12 <br />Mechanical systems located outside of <br />the building thermal envelope <br />C403.13 <br />Service water heating <br />C404 <br />Electrical power and lighting systems <br />C405, except C405.3 <br />Maintenance information and system <br />commissioning <br />C408 <br />Page 5 of 29 <br />